| Fluke 1760 Three-Phase Power Quality Recorders |
| |
The Fluke 1760 Three-Phase Power Quality Recorder is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. Designed for analysis of utility and industrial power distribution systems, in medium- and low-voltage networks, this power quality monitor provides the flexibility to customize thresholds, algorithms, and measurement selections. The 1760 power recorder captures the most comprehensive details on user-selected parameters.
- Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard
- GPS time synchronization: Correlate data with events or datasets from other instruments with precision
- Flexible and fully configurable thresholds and scale factors: Allows user to pinpoint specific issues by defining the detailed criteria for detection and recording of disturbances.
- Uninterrupted power supply (40 minutes): Never miss important events - even record the beginning and end of interruptions and outages to help determine the cause
- 10 MHz, 6000 Vpk waveform capture: Get a detailed picture of even the shortest event
- 2 GB data memory: Enables detailed, simultaneous recording of numerous power parameters for long periods of time
- Comprehensive software included: Provides trend diagrams for root cause analysis, statistical summaries, report writing and real-time data monitoring in the online mode
- Plug and play: Allows quick setup with automatic sensor detection; sensors are instrument powered, eliminating the need for batteries
- 5 MHz, 8000 Vpk waveform capture: Get a detailed picture of even the shortest events
- Rugged field design: Insulated housing and a solid state design with no rotating components enable reliable testing under nearly any conditions
|
|
| |
For Specs: PDF file (Adobe Reader Required)
Phone: (410) 472-2416
Fax: (410) 472-4652
Email: sales@tomwblack.com
|
| |
| | Select from Four 1760 Products: |
|
Product Feature
|
Fluke 1760 Basic
|
Fluke 1760TR Basic
|
Fluke 1760
|
Fluke 1760TR
|
|
Power quality statistics according to EN50160
|
|
|
|
|
|
Voltage event list (dips, swells and interruptions)
|
|
|
|
|
|
Continuous recording of:
|
|
Voltage
|
|
|
|
|
|
Current
|
|
|
|
|
|
Power P, Q, S
|
|
|
|
|
|
Power factor
|
|
|
|
|
|
kWh
|
|
|
|
|
|
Flicker
|
|
|
|
|
|
Unbalance
|
|
|
|
|
|
Frequency
|
|
|
|
|
|
Voltage and current harmonics to the 50th
/ Interharmonics
|
|
|
|
|
|
THD
|
|
|
|
|
|
Mains signaling
|
|
|
|
|
|
Triggered recordings
|
|
|
|
|
|
Online mode (Oscilloscope, transients and events)
|
|
|
|
|
|
Fast transient analysis up to 10 MHz
|
|
|
|
|
|
4, 600V voltage probes
|
|
|
|
|
|
4 dual-range flexible current probes (1000 A / 200 A ac)
|
|
|
|
|
|
GPS time sync receiver
|
|
|
|
|
|
Memory
|
2 GB Flash memory
|
|